Installation, Operation and Maintenance
MODEL F80A
CATEGORY I NATURAL GAS AND LP GAS
MID EFFICIENCY WARM AIR FURNACE
Please read the operating instructions and safety
precautions carefully and thoroughly before installing
and operating your furnace. Keep this manual in a
safe place for future reference.
23-23-0427N-006
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
FURNACE SIZING . . . . . . . . . . . . . . . . . . . . . .3
LOCATION of UNIT . . . . . . . . . . . . . . . . . . . .3
INSTALLATION POSITIONS . . . . . . . . . . . . . . .4
AIR CONDITIONING . . . . . . . . . . . . . . . . . . . .4
INSPECTION/ACCESS PANEL . . . . . . . . . . . . .4
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . .5
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . .5
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . .6
DETERMING COMBUSTION AIR . . . . . . . . . .7
FURNACE VENTING . . . . . . . . . . . . . . . . . . . .8
GAS SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . .12
CONVERSIONS . . . . . . . . . . . . . . . . . . . . . . .13
HIGH ALTITUDE & AIRFLOW
SPECIFICATION TABLES . . . . . . . . . . . . . . . .14
ELECTRICAL SPECIFICATIONS . . . . . . . . . . .15
START UP PROCEDURES/
SEQUENCE OF OPERATION . . . . . . . . . . . . .17
AIR FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . .19
ADJUSTING BLOWER SPEEDS . . . . . . . . . . .19
MAINTENANCE
. . . . . . . . . . . . . . . . . . . . . .
20
TROUBLESHOOTING . . . . . . . . . . . . . . . . . .21
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . .25
TABLE OF CONTENTS
USER’S INSTRUCTION GUIDE
LOCATED AFTER PAGE 25 OF THIS
INSTALLATION, OPERATION AND
MAINTENANCE MANUAL
Model
Serial Number
Date of Purchase
For future reference write down the model, serial
number, and date of purchase. Use these numbers in
any correspondence or service calls concerning your
furnace.
Keep these instructions for future reference.
Vista de página 0
1 2 3 4 5 6 ... 31 32

Resumo do Conteúdo

Página 1 - MODEL F80A

Installation, Operation and MaintenanceMODEL F80A CATEGORY I NATURAL GAS AND LP GASMID EFFICIENCY WARM AIR FURNACEPlease read the operating instructio

Página 2

9MODEL F80AIMPORTANT: THIS FURNACE IS NOT TO BE VENTED IN THESAME CHIMNEY OR VENTING SYSTEM SERVING A SOLIDFUEL APPLIANCE (WOOD OR COAL). IF THE FURNA

Página 3

10WARM AIR FURNACEVENT CONNECTORThe furnace may be vented with a listed single wall or Type B double wall vent connector to a B-Vent or linedmasonry c

Página 4

11MODEL F80AVENT TERMINATIONTerminate all vertical vents with a listed vent cap or roofassembly unless local codes require otherwise. Locate thetermin

Página 5

12WARM AIR FURNACEWARNINGTHIS FURNACE IS FACTORY EQUIPPED TO BURN NATURALGAS ONLY.CONVERSION TO L.P. GAS REQUIRES SPECIAL KIT No.30482.FAILURE TO USE

Página 6

13MODEL F80ACONVERSIONSHIGH ALTITUDEIn the United States, the modifications for high altitude arebased on a 4 percent reduction of input capacity for

Página 7

14WARM AIR FURNACETABLE 3: HIGH ALTITUDE SPECIFICATIONS - CANADAMODELInput x1000ALTITUDEFeetINPUTBTU/hrOUTPUTBTU/hrNAT.ORIFICEL.P.ORIFICE QTY.QTY.234

Página 8

15MODEL F80ASETTING THE MANIFOLD (Outlet) GAS PRESSURE(F92-1003 36G Valve Pressure Check Kit)1. Shut off the gas upstream of valve and move valveswitc

Página 9

16WARM AIR FURNACETHERMOSTAT LOCATIONThe thermostat should be located approximately 5 feet abovethe floor, on an inside wall where there is good natur

Página 10

17MODEL F80ASTART UP PROCEDURESThis furnace is equipped with a hot surface ignition (HSI) device.Each time that the room thermostat calls for heat, th

Página 11 - WARM AIR FURNACE

18WARM AIR FURNACEFigure 10:PiggybackConnectorRemove blue wirefrom HEAT terminal,tape it off, andreplace it with ajumper. Connect theblack wire andjum

Página 12 - Figure 8: Vent Termination

1MODEL F80AINTRODUCTIONThis gas fired midefficiency (non-condensing) furnace is anup flow, counterflow or horizontal flow warm air furnacesuitable for

Página 13

19MODEL F80AADJUSTING BLOWER SPEEDSIf the blower speeds require adjusting, follow these steps:1. Remove the blower compartment door.2. Access the mo

Página 14

20WARM AIR FURNACEWARNINGDISCONNECT THE ELECTRICAL POWER SUPPLY TO THEFURNACE BEFORE ATTEMPTING ANY MAINTENANCE.FAILURE TO DO SO CAN CAUSE ELECTRICAL

Página 15

21MODEL F80AINDUCED BLOWERThe induced blower motor should be inspected and cleanedif necessary. Clear any dust buildup from the ventilationports.CIRCU

Página 16

22WARM AIR FURNACETROUBLESHOOTING SEQUENCE OF OPERATION: WHITE RODGERS INTEGRATED FURNACE CONTROL WITH WHITE RODGERS 36G22 GAS VALVEAPPLY POWER TO APP

Página 18

24WARM AIR FURNACETABLE 11: GENERAL TROUBLESHOOTING WHITE-RODGERS INTEGRATED FAN CONTROLIF AND CHECK or REPAIR Induced blower does not energize 2

Página 19 - Time in Sec. for 1 cu. ft

25MODEL F80ARR3FACTORY SETTING

Página 20

User’s Information ManualMODEL F80A SERIES GAS-FIRED WARM AIR FURNACEFURNACE COMPONENTS . . . . . . . . . . . . . . . . . .1REGULATOR VENT . . . . .

Página 21

1MODEL F80AFURNACE COMPONENTSFigure 1 (below) is provided to help identify thecomponents of your furnace.REGULATOR VENTMost natural gas systems and al

Página 22

2WARM AIR FURNACEWARNINGIMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,SERVICE OR MAINTENANCE CAN CAUSE PROPERTYDAMAGE, PERSONAL INJURY OR DEATHFOR ASS

Página 23 - TROUBLESHOOTING

2WARM AIR FURNACEDANGERWHAT TO DO IF YOU SMELL GAS:• DO NOT TRY TO LIGHT ANY APPLIANCE• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOTUSE ANY PHONE IN YOU

Página 24 - 50V51-250

3MODEL F80AMAINTENANCEAIR FILTERLUBRICATIONMinimal lubrication is required for your furnace. Theinduced blower assembly motors have sealed bearings. T

Página 25

4WARM AIR FURNACESEQUENCE OF OPERATION1. Thermostat, responding to cool room, calls for heat.2. Combustion air blower begins.3. After 15 second pre

Página 26

5The information in this manual supersedes and replaces the previous instruction/operation manual with regards to Warm AirFurnace products. Illustrati

Página 27 - User’s Information Manual

3MODEL F80AFURNACE SIZINGThe maximum hourly heat loss for each heated space shallbe calculated in accordance with the procedures describedin Manual J

Página 28

4WARM AIR FURNACEUPFLOW INSTALLATIONThis furnace comes assembled for installation in the upflowposition and ready for vertical venting. In the event t

Página 29

5MODEL F80ADIMENSIONS (IncheMODEL WIDTH DEPTH HEIGHT SUPPLYA35-2 14-1/2 29 35 13-1/2 x 1950-3 14-1/2 29 35 13-1/2 x 1970-3 16 29 35 15 x 1970-4 17-1/2

Página 30

6WARM AIR FURNACEDUCTWORK STEPS:1. Position the furnace to minimize ductwork length andfittings.2. Cut open a return air inlet. The choices are:a) eit

Página 31

7MODEL F80ADANGERREAD, UNDERSTAND AND FOLLOW ALL INSTRUCTIONSIN THIS SECTION. FAILURE TO PROPERLY VENT ORSUPPLY COMBUSTION AIR TO THIS FURNACE CANCAUS

Página 32

8WARM AIR FURNACEWARNINGSELECT APPROPRIATE VENTING MATERIALS ANDENSURE PROPER CLEARANCES TO COMBUSTIBLES.INADEQUATE VENTING OR FAILURE TO MAINTAINPROP